From two test points measuring the time-to-trip and injected fault current and the known IEEE/IEC curve determine the best fit Time Multiplier (TMS) and Pickup (PU) settings.

Notifications You must be signed in to change notification settings

Top-Dog/HV-Overcurrent-OC-Relay-Settings

Folders and files

NameName
Last commit message
Last commit date

Latest commit

 

History

4 Commits
 
 
 
 

Repository files navigation

HV-Overcurrent-OC-Relay-Settings

Overcurrent (OC) protection is a standard protection function offered by many relays in the HVAC power industry. However, sometimes field results arrive incomplete or incompressible, or electro-mechanical relays are used which do not have any recorded curve settings. This is a utility script to help find the best fit OC configuration settings by supplying an initial estimate/best guess for the settings.

From (1) two test points measuring the time-to-trip and injected fault current, (2) the known IEEE/IEC curve, (3) and CT ratio determine the best fit Time Multiplier (TMS) and Pickup (PU) settings.

Requires the SymPy libary. Get it using: pip install sympy

The user just needs to change the configuration options to match their test case, for example:

################## User Supplied Parameters ##################
CTRatio = 400/1
point1 = Point(0.7*CTRatio, 1.923)      # Test point one (x,y)
point2 = Point(3.5*CTRatio, 0.219)      # Test point two (x,y)
curve = Curve("IEC very inverse Class B")
hint = [0.2, 0.1]       # The approximate [PU, TMS] settings
##############################################################

About

From two test points measuring the time-to-trip and injected fault current and the known IEEE/IEC curve determine the best fit Time Multiplier (TMS) and Pickup (PU) settings.